BASIC Module (DB/BAS Compatible)
MVI56-BAS
This single-slot module is a powerful solution that allows the large installed base of legacy BASIC programs for the 1771-DB and 1747-BAS modules to be migrated to the ControlLogix platform with minimal effort.
Features and Benefits
The MVI56-BAS module allows you to:
- Create BASIC programs to transfer data between the ControlLogix and the MVI56-BAS module
- Create foreign device interface for specific applications and easily integrate the device with the ControlLogix processor
- Interface to many devices that use ASCII interface to a ControlLogix backplane such as modems, printers, bar code readers, and scales.
- Save ControlLogix processor memory by running math algorithms
The module acts as DF1 full-duplex device or a DF1 half-duplex slave.
The BASIC programs are stored in the MVI56-BAS Compact Flash disk allowing the user to easily backup the BASIC programs to another Compact Flash disk or to a local PC. Up to 24065 Bytes of RAM memory are available.
The module contains three ports:
- DH-485: DH-485 communication or BASIC program transfer
- PRT1: ASCII communication or program port
- PRT2: ASCII communication or DF1 communication
The user can either create the BASIC programs using the command line, then saving it Compact Flash, or create the program on a PC and download it to the MVI56-BAS module. The user can also configure the module to execute a BASIC program automatically at power up.
General Specifications
- Single Slot - 1756 backplane compatible
- The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
- Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
- Configuration data obtained from configuration text file downloaded to module. Sample configuration file included
- Local or remote rack
Applications
The MVI56-BAS module allows existing legacy BASIC programs to be migrated from the 1771 and 1746 platforms to the ControlLogix platform. This provides interface capability for many devices using the ASCII interface to the ControlLogix backplane including:
- Bar code scanner interfaces
- Weigh scale interfaces
- Legacy ASCII protocol connections
- Terminal port emulation
- Printer driver (alarm/status printer)
Functional Specifications
- Supports BASIC-52 Programming language
- Stores BASIC programs on Compact Flash disk
- Supports 24064 bytes of RAM
- Easy BASIC program backup
DF1 Communications
- PRT2 can be enabled and configured for DF1 Communications through BASIC calls
- Uses ladder logic to transfer data between the DF1 device and the ControlLogix processor
- PRT2 port can be configured to act as a full-duplex device or half-duplex slave.
The MVI56-BAS can send the following DF1 commands:
- PLC-2 unprotected READ command
- PLC-2 unprotected WRITE command
- PLC-3 word range READ command
- PLC-3 word range WRITE command
- PLC-5 typed READ command
- PLC-5 typed WRITE command
The MVI56-BAS accepts the following commands:
- PLC (word range writes)
- PLC (typed writes)
- PLC (unprotected write)
- SLC 5/02 (unprotected write)
- SLC 5/02 (typed writes)
DH-485 Communications
- The MVI56-BAS DH-485 port can be used to interface the ControlLogix processor with DH-485 Devices
- Rockwell Automation AIC+ device is required (user-supplied)
- Ladder logic is required to transfer data between the ControlLogix processor and remote data file or common interface file
Hardware Specifications
|
Specification
|
Description
|
|
Backplane Current Load
|
800 mA maximum @ 5 Vdc
|
|
Operating Temperature
|
0° C to 60° C (32° F to 140° F)
|
|
Storage Temperature
|
-40° C to 85° C (-40° F to 185° F)
|
|
Shock:
|
30g Operational
50g non-operational Vibration: 5 g from 10 to 150 Hz
|
|
Relative Humidity
|
5% to 95% RH, (with no condensation)
|
|
LED Indicators:
|
Module Status
Backplane Transfer Status
Application Status Serial Activity
|
|
Application Serial ports (P1, P2)
|
|
|
|
Full hardware handshaking control, providing radio, modem, and multi-drop support
|
|
Software configurable communication parameter
|
Baud rate: 110 to 115,200 baud depending on protocol
Parity: None, Odd or Even
Data Bits: 5, 6, 7, or 8
Stop Bits: 1 or 2
RTS On/Off Delay: 0 to 65535 ms RS-232 handshaking configurable
|
|
App Ports (P1, P2)
|
RJ45 (DB-9M with supplied cable)
RS-232, 485, and 422 (jumper selectable) 500V optical isolation from backplane
|
|
CFG Port
|
RJ45 (DB-9M with supplied cable) RS-232 only
|
|
Shipped with unit
|
RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for the debug port
|
Ordering Information
| MVI56-BAS |
BASIC Module (DB/BAS Compatible) |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.
Sales and Support:
|