Modbus TCP/IP Client/Server Communication Module
MVI46-MNET
The MVI46 Modbus TCP/IP Communication Module is designed to allow SLC processors to interface easily with other Modbus TCP/IP protocol-compatible devices using client and server functionality.
Compatible devices include not only Modicon processors (which support the Modbus TCP/IP protocol) but also a wide assortment of other clients and server devices.
Features and Benefits
The MVI46-MNET module is a single slot solution that provides a powerful connection between Rockwell Automation's SLC processor and Modbus TCP/IP network applications.
The TCP/IP Modbus network applications include those networks hosted by Modicon Quantum processors, networks controlled by operator interface software packages, and the growing number of manufactured devices that support this protocol. The module acts as an input/output module between the Modbus TCP/IP network and the Rockwell Automation backplane. The data transfer from the processor is asynchronous from the actions on the Modbus TCP/IP network. A 5000-word register space in the module exchanges data between the processor and the Modbus TCP/IP network.
- Support for the storage and transfer of up to 5000 registers to/from the SLC processor using M0/M1 data file transfer
- User-definable module memory usage
- 10/100 MB Ethernet compatible interface
- Configurable parameters for the client and server applications and floating point support
General Specifications
- Single Slot - 1746 backplane compatible (Local or extended I/O rack only. Remote rack not supported)
- The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module using M0/M1 files
- Ladder Logic is used for data transfer between module and processor. Sample ladder file included
- Configuration data obtained from configuration text file downloaded to module. Sample configuration file included
Applications
With the growing trend of Ethernet technology in the industrial marketplace, this product has a wide variety of application uses.
- Food processing
- Petrochemical
- Pulp and paper
- Automobile manufacturing
- Water and Wastewater
- Oil and Gas
- Power and Electric
Functional Specifications
General Protocol specifications
|
Type
|
Specifications
|
|
Floating Point Data
|
Floating point data movement supported, including configurable support for Enron and Daniels floating poiont implementations
|
|
Supported Function Codes
|
Function Code Descriptions
|
|
FC 1
|
Read Coil Status (Bits)
|
|
FC 2
|
Read Input Status (Bits)
|
|
FC 3
|
Read Input Registers
|
|
FC 4
|
Read Holding Registers
|
|
FC 5
|
Write Single Coil (Bit)
|
|
FC 6
|
Write Single Holding Register
|
|
FC 15
|
Write Multiple Coils (Bits)
|
|
FC 16
|
Write Multiple Holding Registers
|
Modbus Server Protocol Specifications
The server driver supports up to ten (10) connections to Modbus TCP/IP Clients using Service Port 502 with the standard MBAP protocol, and up to an additional ten (10) Clients using an other service port for Encapsulated Modbus protocol.
Modbus TCP/IP Client
The Client driver supports the active reading and writing of data with Modbus TCP/IP compatible devices. One Client with up to 100 total commands. (Allows connections to as many as 100 Servers)
Hardware Specifications
|
Ethernet and CFG Ports
|
|
|
Ethernet Port
|
RJ45 connection
10/100 Mbit Ethernet support (auto-sensing)
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 seconds, applied as specified in section 5.3.2 of IEC 60950: 1991 Ethernet Broadcast Storm Resiliency = less than or equal to 5000 [ARP] frames-per-second and less than or equal to 5 minutes duration
|
|
CFG Port
|
RJ45 (DB-9M with supplied cable) RS-232 only
|
|
Shipped with unit
|
RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for debug port
|
|
Specification
|
Description
|
|
Backplane Current Load
|
800 ma @ 5V (from backplane)
|
|
Operating Temperature
|
0 to 60° C (32 to 140° F)
|
|
Storage Temperature
|
-40 to 85° C (-40 to 185° F)
|
|
Shock
|
30g operational, 50g non-operational
|
|
Relative Humidity
|
5 to 95% (non-condensing)
|
|
Vibration
|
5g from 10 to 50 Hz
|
|
Processor
|
Compatible with Rockwell Automation SLC 5/02 M0/M1 capable processors or newer.
|
|
LED indicators
|
Module status, Backplane transfer status, Application status, Serial activity and error LED status
|