IEC 60870-5-103 Master Communication Module with Reduced Data Block
MVI56-103MR
The MVI56 IEC 60870-5-103 Master Communication Module with Reduced Data Block allows Rockwell Automation ControlLogix backplane I/O compatible processors to interface easily with IEC 60870-5-103 compatible devices. Devices commonly supporting the protocol include relays, breakers, sub-station Communication Modules and other serial communication devices used in power monitoring.
This module uses a small I/O data area for data transfer between the module and the ControlLogix processor, making it ideal for ControlNet applications.
Features and Benefits
The MVI56-103MR supports up to 32 total field devices between the module's two IEC 60870-5-103 Master ports. The module's communication ports can each be independently configured, allowing two separate field networks to be implemented. The field device data is exchanged between the MVI module and the ControlLogix processor over the backplane.
General Specifications
- Single Slot - 1756 backplane compatible
- The module is recognized as an Input/Output module and has access to processor memory for data transfer between processor and module
- Ladder Logic is used for data transfer between module and processor. Sample ladder file included.
- Configuration data obtained from configuration text file downloaded to module. Sample configuration file included
- Local or remote rack
Applications
The MVI56-103MR module is the ideal solution for many applications where IEC protocol connectivity must be added to a ControlLogix system. The IEC solution is designed to address the expanding interest in the IEC protocol and the use of IEC compatible devices in industrial applications such as those in the water/wastewater power and oil & gas industries.
Compatible devices include relays, breakers, sub-station Communication Modules and other serial communication devices.
Functional Specifications
The MV56-103MR module supports the IEC 60870-5-103 protocol to the following specifications:
- The IEC 60870-5-103 communication driver is built in accordance to the approved IEC specification
- This module uses a small I/O data area for data transfer between the module and the ControlLogix processor.
- Module memory usage that is completely user definable
- The module has two independent master ports, each configurable via a simple configuration file
- Supports up to 32 sessions (controlled devices) between the two ports
- Supports up to five sectors (separate databases) for each session, with individual database definition for each sector
- Total of 1000 user configurable commands to control data transfer to/from devices (controlled devices)
- Supports clock synchronization from/to the processor
- Event data received from the Control Devices updates the module database (Date and Time stamping is not stored or used by module)
- Class 1 and Class 2 delay parameter are configurable for each session
- An IEC Interoperability Document for the module is available from the web site, which fully documents data types supported by the module
Hardware Specifications
|
Specification
|
Description
|
|
Backplane Current Load
|
800 mA maximum @ 5 Vdc
|
|
Operating Temperature
|
0° C to 60° C (32° F to 140° F)
|
|
Storage Temperature
|
-40° C to 85° C (-40° F to 185° F)
|
|
Shock:
|
30g Operational
50g non-operational Vibration: 5 g from 10 to 150 Hz
|
|
Relative Humidity
|
5% to 95% RH, (with no condensation)
|
|
LED Indicators:
|
Module Status
Backplane Transfer Status
Application Status Serial Activity
|
|
Application Serial ports (P1, P2)
|
|
|
|
Full hardware handshaking control, providing radio, modem, and multi-drop support
|
|
Software configurable communication parameter
|
Baud rate: 110 to 115,200 baud depending on protocol
Parity: None, Odd or Even
Data Bits: 5, 6, 7, or 8
Stop Bits: 1 or 2
RTS On/Off Delay: 0 to 65535 ms RS-232 handshaking configurable
|
|
App Ports (P1, P2)
|
RJ45 (DB-9M with supplied cable)
RS-232, 485, and 422 (jumper selectable) 500V optical isolation from backplane
|
|
CFG Port
|
RJ45 (DB-9M with supplied cable) RS-232 only
|
|
Shipped with unit
|
RJ45 to DB-9M adapter cable and 6-foot RS-232 configuration cable for the debug port
|
Ordering Information
| MVI56-103MR |
IEC 60870-5-103 Master Communication Module with Reduced Data Block |
| |
|
| To place an order, please contact your local ProSoft Technology, Inc. distributor. For a list of ProSoft distributors near you, click here. |
Distributors:
Place your order by email to orders@prosoft-technology.com:, fax to +1 661-716-5101.